FS17—-450/750 V PVC Insulated Cable

Application of  FS17 Cable

Cables suitable for electric power systems in construction and buildings, in order to limit fire and smoke production. Suitable for fixed and protected installation in, or on, lighting or control gear for voltage up to 1000 V AC; up to 750 V DC to earth. For further details, please refer to CEI 20-40 standard.

 

Rated voltage: 450/750 V
Conductors: Cu rope, class 5 acc. to EN 60228
Insulation: PVC compound, S17 quality
CPR class: Cca – s3,d1,a3
Bending radius (min): 4D
Min. laying temperature: -5°C
Min. operating temperature: -10°C
Max. conductor temperature: 70°C
Max. short-circuit temperature:160°C

CROSS SECTION MAX RESISTANCE AT 20°C CURRENT CAPACITY IN AIR AT 30°C INSULATION THICKNESS OUTER DIAM. (APPROX) METAL WEIGHT CABLE WEIGHT (APPROX)
mm² Ω/km A mm mm kg/km kg/km
1×0,75 26,0 6 0,6 2,3 7,2 12,1
1×1,0 19,5 10 0,6 2,4 9,6 14,8
1×1,5 13,3 17,5 0,7 3,0 14,4 21,5
1×2,5 7,98 24 0,8 3,6 24,0 34,0
1×4 4,95 32 0,8 4,2 38,4 50,3
1×6 3,30 41 0,8 4,7 57,6 71,4
1×10 1910 57 1,0 6,1 96,0 118,1
1×16 1210 76 1,0 7,2 153,6 180,0
1×25 0,780 101 1,2 8,4 240,0 279,2
1×35 0,554 125 1,2 9,5 336,0 381,5
1×50 0,386 151 1,4 11,3 480,0 543,2
1×70 0,272 192 1,4 12,6 672,0 744,6
1×95 0,206 232 1,6 14,7 912,0 1008,9
1×120 0,161 269 1,6 16,2 1152,0 1259,6
1×150 0,129 300 1,8 18,1 1440,0 1574,9
1×185 0,106 341 2,0 20,2 1776,0 1942,2
1×240 0,0801 400 2,2 22,9 2304,0 2512,2