1 GENERAL APPLICATIONS:
Cables for overhead power distribution systems mainly for public distribution.
2 CONDUCTOR:
AL stranded class 2 to IEC 60228
3 INSULATION:
XLPE Cross-linked polyethylene
Test voltage: 4 kV a.c. (5 min.)
Maximum temperature rating of the conductor : +90 °C
Short-circuit temperature of the conductor: 250 °C (t <5s)
Maximum pulling force over conductor (N): over conductors 30 x Section mm2
Didn’t find the spec you were looking for? Please send us an email: sales@huadongcablegroup.com and our manager will reply to you as soon as possible.
Cross Section | Nominal overall diameter | Nominal weight | Minimum bending radius | Maximum current rating Air 30 ºC |
No x mm2 | mm | kg/km | mm | A |
2×16 | 15,0 | 136 | 70 | 85 |
3×16 | 16,0 | 204 | 70 | 75 |
4×16 | 18,0 | 272 | 70 | 75 |
5×16 | 21,0 | 325 | 84 | 75 |
4×25 | 18,5 | 407 | 85 | 97 |
4×25+16 | 19,0 | 475 | 85 | 100 |
4×25+2×16 | 21,0 | 527 | 88 | 100 |
4×35 | 24,7 | 549 | 95 | 120 |
4×35+16 | 26,0 | 612 | 100 | 120 |
4×35+2×16 | 28,0 | 677 | 135 | 120 |
4×50 | 29,5 | 714 | 130 | 150 |
4×50+16 | 30,5 | 782 | 135 | 150 |
4×50+2×16 | 32,0 | 782 | 135 | 150 |
4×70 | 31,0 | 892 | 150 | 190 |
4×70+16 | 33,0 | 1.09 | 160 | 190 |
4×70+2×16 | 35,0 | 1.09 | 160 | 190 |
4×95+16 | 39,0 | 1.404 | 170 | 230 |