FR-N1 X1G1-AR Cable (Aluminium)
Voltage: 0.6/1kV
Conductor: RM: Class 2 round stranded aluminium
Insulation: XLPE
Inner Sheath: Halogen free tape or halogen free polymer compound
Outer Sheath: Halogen-free polymer compound
Outer Sheath Colour: Green
STANDARDS:
NF C 32-323, IEC 60502-1, IEC 60754-1, IEC 61034, IEC
60754-2, HD 308 s2
Flame retardant according to NFC 32-070, IEC 60332-3-24
Applications: The FR-N1 X1G1-AR low voltage aluminium fire retardant power cable is recommended for use in public and industrial settings whenever reduced fumes, toxic and corrosive gases emissions are required in case of fire. May be used in industrial settings and in building risers. Can be used for static applications in the open air, in pipes, or in cable trays and trenches.
FR-N1 X1G1 Cable (Copper)
Voltage: 0.6/1kV
Conductor: RE: Class 1 round solid copper; RM: Class 2 round stranded copper
Insulation: XLPE
Inner Sheath: Halogen free tape or halogen free polymer compound
Outer Sheath: Halogen-free polymer compound
Outer Sheath Colour: Green
STANDARDS:
NF C 32-323, IEC 60228, HD 308 s2, IEC 60754-1,
IEC 61034, IEC 60754-2
Flame retardant according to IEC 60332-1
Applications: The FR-N1 X1G1 is a low voltage fire resistant cable suitable for hotels, hospitals, underground railways, airports etc. to protect people and technical building equipment in the event of a fire if circuit integrity is not required. Not suitable for installations underground or in water.
FR-N1 X1G1-AR Cable (Aluminium) Partial data table
| NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm² | CONDUCTOR TYPE | NOMINAL WEIGHT kg/km |
| 1 | 16 | RM | 110 |
| 1 | 25 | RM | 157 |
| 1 | 35 | RM | 193 |
| 1 | 150 | RM | 628 |
| 1 | 400 | RM | 1615 |
| 1 | 500 | RM | 1940 |
| 2 | 16 | RM | 417 |
| 2 | 25 | RM | 615 |
| 2 | 35 | RM | 745 |
| 3 | 50+35 | RM | 1170 |
| 3 | 150 | RM | 2760 |
| 3 | 185+70 | RM | 3680 |
| 4 | 25 | RM | 785 |
| 4 | 120 | RM | 2730 |
| 4 | 240 | RM | 5315 |
FR-N1 X1G1 Cable (Copper) Partial data table
| NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm² | NOMINAL OVERALL DIAMETER mm | NOMINAL WEIGHT kg/km |
| 1 | 50 | 12.7 | 510 |
| 1 | 70 | 14.5 | 720 |
| 1 | 95 | 16.5 | 975 |
| 2 | 6 | 12.4 | 270 |
| 2 | 10 | 14.1 | 385 |
| 2 | 16 | 16.2 | 545 |
| 3 | 240 | 54.2 | 8555 |
| 3 | 240/95 | 55.2 | 9250 |
| 3 | 300 | 59.9 | 10700 |
| 4 | 185 | 53.9 | 8530 |
| 4 | 240 | 60.1 | 10970 |
| 4 | 300 | 66.7 | 13770 |
| 5 | 10 | 17.8 | 715 |
| 5 | 16 | 20.3 | 1035 |
| 5 | 25 | 24.5 | 1580 |