Application
N07V3V3-F PVC Building Site Cable – This cable is suitable for connecting electrical equipment particularly on building sites. It is used in dry and damp locations, outdoors and in areas with explosion hazard.
AT-N07V3V3-F Flexible PVC cable for the use in low temperature areas, even at temperatures of-35C°. Cable for mobile laying particularly suitable for areas with cold temperatures. Its excellent flexibility makes it suitable for many uses (extension cords, cable reels, etc.). Excellent oil and mechanical resistance.
Construction:
1 ….. fine-stranded bare copper
2 ….. core insulation of cold-resistant polyvinylchloride(PVC)
3 ….. outer sheath of cold-resistant polyvinylchloride (PVC), yellow
Technical data:
Nominal voltage Uo/U: 450 / 750 V
Temperature range in motion: -35°C till +70°C
Operating temperature short circuit: 160°C
Short circuit time max.: 5 [sec]
Flammability standard EN 60332-1-2
Standards:
ÖVE / Östandard E8241-55
DIN EN 60228 class 5 (construction)
HD 308 S2 (core identification)
Nominal voltage Uo/U: 450/750 V
Conductor: Plain copper flexible wire, class 5
Insulation: Special thermoplastic compound resistant to low temperatures
Outer sheath: Special thermoplastic compound resistant to low temperatures, with excellent oil resistance
Cores colour: HD 308 Standard
Sheath colour: Yellow, orange, red
Maximum operating temperature: 70°C
Minimum operating temperature: -35°C (without mechanical stress)
Maximum short circuit temperature: 160°C
Maximum tensile stress: 15 N/mm2
Minimum bending radius: 6 x maximum external diameter
N07V3V3-F Parameter List
Number of cores and nominal cross section mm² | Copper figure | Cond. construction (appr. value) mm | Overall diameter appr. mm | Weight |
kg/km | appr. kg / km | |||
2 X 1,5 | 30 | 30 x 0,26 | 9,0 | 85 |
3 G 1,5 | 45 | 30 x 0,26 | 10,5 | 132 |
4 G 1,5 | 60 | 30 x 0,26 | 11,6 | 161 |
5 G 1,5 | 75 | 30 x 0,26 | 12,8 | 185 |
3 G 2,5 | 75 | 50 x 0,26 | 12,4 | 197 |
4 G 2,5 | 100 | 50 x 0,26 | 13,8 | 238 |
5 G 2,5 | 125 | 50 x 0,26 | 15,2 | 291 |
5 G 4 | 200 | 56 x 0,31 | 17,8 | 420 |
5 G 6 | 300 | 84 x 0,31 | 19,9 | 598 |
5 G 10 | 500 | 80 x 0,41 | 26,0 | 1.051 |
5 G 16 | 800 | 128 x 0,41 | 29,9 | 1.442 |
AT-N07V3V3-F Parameter List
Formation | Approx. conductor Ø | Average insulation thickness | Average sheath thickness | Approx. production Ø | Approx. cable weight | Max. electrical resistance at 20°C |
n° x mm2 | mm | mm | mm | mm | kg/km | ohm/ km |
3 x 1 | 1,3 | 0,8 | 1,4 | 9,2 | 110 | 19,5 |
3 x 1,5 | 1,6 | 0,8 | 1,6 | 10,1 | 140 | 13,3 |
3 x 2,5 | 1,9 | 0,9 | 1,8 | 12,0 | 210 | 7,98 |
3 x 4 | 2,5 | 1,0 | 1,9 | 13,8 | 280 | 4,95 |
3 x 6 | 3,0 | 1,0 | 2,1 | 15,4 | 370 | 3,3 |
3 x 10 | 4,0 | 1,2 | 3,3 | 20,6 | 590 | 1,91 |
3 x 16 | 5,0 | 1,2 | 3,5 | 23,7 | 820 | 1,21 |
4 x 1 | 1,3 | 0,8 | 1,5 | 10,1 | 135 | 19,5 |
4 x 1,5 | 1,6 | 0,8 | 1,7 | 11,1 | 170 | 13,3 |
4 x 2,5 | 1,9 | 0,9 | 1,9 | 13,1 | 250 | 7,98 |
4 x 4 | 2,5 | 1,0 | 2,0 | 15,1 | 350 | 4,95 |
4 x 6 | 3,0 | 1,0 | 2,3 | 17,0 | 460 | 3,3 |
4 x 10 | 4,0 | 1,2 | 3,4 | 22,7 | 710 | 1,91 |
4 x 16 | 5,0 | 1,2 | 3,6 | 25,9 | 1010 | 1,21 |
5 x 1 | 1,3 | 0,8 | 1,6 | 11,1 | 160 | 19,5 |
5 x 1,5 | 1,6 | 0,8 | 1,8 | 12,2 | 205 | 13,3 |
5 x 2,5 | 1,9 | 0,9 | 2,0 | 14,5 | 300 | 7,98 |
5 x 4 | 2,5 | 1,0 | 2,2 | 17,0 | 440 | 4,95 |
5 x 6 | 3,0 | 1,0 | 2,5 | 18,9 | 580 | 3,3 |
5 x 10 | 4,0 | 1,2 | 3,6 | 25,1 | 1000 | 1,91 |
5 x 16 | 5,0 | 1,2 | 3,9 | 28,7 | 1390 | 1,21 |