header-logo

HUADONG CABLE GROUP

Professional Cables and Wires Manufacturer in China

600 Volts AL/CU Service Entrance (SE) Cable (SER/SEU)

Also known as:

Type SE, Style SER and SEU Service Entrance Cable;
Copper Aluminum Service Entrance (SE) Cable;
Ground service entrance cable;
SEU: Service Entrance cable, Unarmored;
SER: Service Entrance cable with Reinforcement tape;

APPLICATIONS OF AL/CU Service Entrance (SE) Cable

service entrance cable is used to convey power from the service drop to the meter base and from the meter base to the distribution panelboard; however, it may be used in all applications where Type SE cable is permitted. SE SER may be used in wet or dry above ground locations at temperatures not to exceed 90°C. The voltage rating is 600 volts.

600 Volts Aluminum Service Entrance (SE) Cable

sales@huadongcablegroup.com

 

 

CONSTRUCTION:
Type SE cable is constructed with AA-8000 series aluminum alloy, compacted stranded conductors. The conductors are covered with a sunlight resistant Type XHHW-2 or TypeTHHN/THWN-2-insulation.
A reinforcement tape is wrapped around the conductors for added strength and conformity. A gray sunlight-resistant polyvinyl chloride (PVC) outer jacket covers the entire assembly.
Style SEU cable has two phase conductors surrounded by a concentric neutral while the SER style has two, three or four phase conductors and a bare neutral.
Style SER Cable’s phase conductors are identified by a colored stripe on the insulation.
3 conductor – Black and Black with Red Stripe
4 conductor – Black, Black with White Stripe and Black with Red Stripe
5 conductor – Black, Black with White Stripe, Black with Red Stripe and Black with Blue Stripe

Standards:
ASTM- B-800 and B-801
UL Standard 44 for XHHW-2
UL Standard 83 for THHN/THWN-2
Federal Specification A-A-59544
National Electrical Code, NFPA 70, 2011 Edition
RoHS

 

 

600 Volts Copper Service Entrance (SE) Cable

sales@huadongcablegroup.com

 

CONSTRUCTION:
Type SE cable is constructed with sunlight resistant Type XHHW-2 conductors or Type THHN/THWN conductors.
Copper conductors are annealed (soft) copper. Cable assembly plus reinforcement tape are jacketed with sunlight resistant gray polyvinyl chloride (PVC).
Available as 1 conductor with a concentric ground, 2 conductor with a round or concentric ground, or 3 conductor with a bare ground. SE cable is jacketed with gray sunlight resistant polyvinyl chloride (PVC).

Standards:
ASTM- All applicable standards
UL Standard 44 for XHHW-2 conductors
UL Standard 83 for THHN/THWN conductors
UL Standard 854
Federal Specification A-A-59544
National Electrical Code, NFPA 70. 2011 Edition
RoHS/ REACH

 

 

Aluminum Service Entrance (SE) Cable

Aluminum Service Entrance (SE) Cable
Conductor Stranding Nominal O.D. (Mils) Allowable Ampacities Approximate Net Weight Per 1000′ (Lbs) Standard Package
Size/Const. AWG or kcmil Phase Conductor & Neutral Equipment Ground Conductor 60°C 75°C 90°C Dwelling
SER Aluminum Two-Conductor With Bare Ground (Formerly referred to as “EZ-SE”)
6-6-6 7 650 40 50 60 150 B
4-4-4 7 745 55 65 75 203 B
4-4-6 7 745 55 65 75 203 B
2-2-2 7 864 75 90 100 100 290 B
SER Aluminum Three Conductor With Bare Ground (Formerly referred to as “Four Conductor”)
8-8-8-8 1 1 612 30 40 45 136 B
6-6-6-6 7 7 717 40 50 60 196 B
4-4-4-6 7 7 823 55 65 75 252 B
2-2-2-4 7 7 956 75 90 100 100 359 B
1-1-1-3 8 7 1079 85 100 115 110 449 C
1/0-1/0-1/0-2 10 1 1168 100 120 135 125 540 C
2/0-2/0-2/0-1 12 1 1264 115 135 150 150 652 C
3/0-3/0-3/0-1/0 16 1 1371 130 155 175 175 786 C
4/0-4/0-4/0-2/0 19 1 1496 150 180 205 200 960 C
250-250-250-3/0 22 1 1839 170 205 230 225 1458 C
SER Aluminum Four Conductor With Bare Ground (Formerly referred to as “Five Conductor”)
2-2-2-2-4 6 7 1059 75 90 100 100 452 B
2/0-2/0-2/0-2/0-1 12 1 1404 115 135 150 150 827 C
4/0-4/0-4/0-4/0-2/0 19 1 1672 150 180 205 200 1228 C
250-250-250-250-3/0 22 1 1847 170 205 230 225 C
Conductor Stranding Nominal O.D. (Mils) Allowable Ampacities Approximate Net Weight Per 1000′ (Lbs) Standard Package
Phase Conductor & Neutral Equipment Ground Conductor 60°C 75°C 90°C Dwelling
Size/Const. AWG or kcmil
SEU Aluminum Two Conductor With Bare Conentric Ground (Formerly referred to as “Three Conductor”)
6-6-6 7 8 430×687 40 50 60 145 B,C,E
4-4-4 7 12 499×800 55 65 75 198 B
4-4-6 7 15 474×775 55 65 75 181 B
2-2-2 7 14 569×925 75 90 100 100 283 B,C,G
2-2-4 7 18 554×910 75 90 100 100 259 B,C,G
2/0-2/0-2/0 18 18 736×1221 115 135 150 150 514 C
2/0-2/0-1 18 14 720×1205 115 135 150 150 468 C
4/0-4/0-4/0 18 18 878×1462 150 180 205 205 765 C
4/0-4/0-2/0 18 18 835×1419 150 180 205 205 691 C
Table values reflect XHHW-2 conductors. Allowable ampacities shown are for general use as specified by the National Electrical Code, 2011 Edition, Section 310.15.
60°C – When terminated to equipment for circuits rated 100 amperes or less or marked for 14 through 1 AWG conductors. See NEC Article 338.10 (B)(4).
75°C  – When terminated to equipment for circuits rated 100 amperes or marked for conductors larger than 1 AWG  conductors. Package Codes: B – 1,000′ C- 500′ E-250′ G-200′
May not apply, see NEC Article 338.10 (B)(4).
90°C – Wet or dry locations. For ampacity de-rating purposes.
Dwelling – For units, conductors shall be permitted at listed ampacities as 120/240-volt, 3-wire, single-phase services and feeders per NEC Article  310.15.
*For compact-stranded construction, the number of wires, as permitted by UL Standard 854 and ASTM B-801 may be reduced as follows: 19-wire constructions – 18 wires minimum.

Copper Service Entrance (SE) Cable

Conductor Stranding Nominal O.D. (Mils) Allowable Ampacities Approximat e Net Weight Per 1000′ (Lbs) Standard Package
60°C 75°C 90°C Dwelling
Phase Conductor & Neutral Equipment Ground Conductor
Size/Const. AWG or kcmil
SER Two Conductor With Bare Contentric Ground (Formerly referred to as “Three Conductor”)
8-8-8 7 586 40 50 55 231 B
6-6-6 7 669 55 65 75 338 B
4-4-4 7 764 70 85 95 100 498 B
3-3-3 7 829 85 100 110 110 611 B
2-2-2 7 896 95 115 130 125 752 B
1-1-1 19 1021 110 130 150 150 948 C
1/0-1/0-1/0 19 1114 125 150 170 175 1169 C
2/0-2/0-2/0 19 1209 145 175 195 200 1444 C
3/0-3/0-3/0 19 1317 165 200 225 225 1792 C
4/0-4/0-4/0 19 1438 195 230 260 250 2226 C
SER Three Conductor With Bare Ground (Formerly referred to as “Four Conductor”)
8-8-8-8 7 7 645 40 50 55 286 B
6-6-6-6 7 7 738 55 65 75 424 B
4-4-4-6 7 7 844 70 85 95 100 585 B
3-3-3-5 7 7 910 85 100 110 110 719 B
2-2-2-4 7 7 984 95 115 130 125 887 B
1-1-1-3 19 7 1132 110 130 150 150 1117 C
1/0-1/0-1/0-2 19 19 1235 125 150 170 175 1382 C
2/0-2/0-2/0-1 19 19 1342 145 175 195 200 1713 C
3/0-3/0-3/0-1/0 19 19 1462 165 200 225 225 2129 C
4/0-4/0-4/0-2/0 19 19 1598 195 230 260 250 2650 C
Table values reflect XHHW-2 conductors Package Code: A-250′ B-500′ C-1,000′ D-100 E- 150′
Allowable ampacities shown are for general use as specified by the National Electrical Code, 2011 Edition, section 310.15 and 240.4(D).
Unless the is marked for use at higher temperatures the conductor ampacities shall be limited to the following per NEC 110.14(C)
60 °C When terminated to equipment for circuits rated 100 amperes or less or marked for 14 – 1 AWG conductors.
75 °C When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.
90 °C XHHW wet or Dry locations for ampacity adjustment purposes using NEC section 310.15 For dwelling ampacity use section 310.15(B)(7)
Conductor Stranding Nominal O.D. (Mils) Allowable Ampacities Approximate Net Weight Per 1000′(Lbs) Standard Package
Size/Const. AWG or kcmil Phase Conductor & Neutral Equipment Ground Conductor 60°C 75°C 90°C Dwelling
SEU  Two Conductor With Bare Concentric Ground (Formerly referred to as “Three Conductor”)
10-10-10 1 12 428 X 283 30 30 30 127 ABC
8-8-8 7 8 587 X 380 40 50 60 211 ABC
6-6-6 7 12 659 X 416 55 65 75 308 BCE
4-4-4 7 12 815 X 506 70 85 95 100 471 BCE
3-3-3 7 12 883 X 548 85 100 110 110 583 B
2-2-2 7 15 994 X 578 95 115 130 125 718 BD
1-1-1 19 14 1093 X 664 110 130 150 150 904 B
1/0-1/0-1/0 19 18 1179 X 707 125 150 170 175 1123 BC
2/0-2/0-2/0 19 18 1283 X 767 145 175 195 200 1379 BC
3/0-3/0-3/0 19 14 1429 X 862 165 200 225 225 1712 BD
4/0-4/0-4/0 19 18 1541 X 918 195 230 260 250 2146 BC
SEU  Two Conductor With Bare Concentric Ground (Formerly referred to as “Three Conductor”) (Reduced Neutral)
6-6-8 7 8 659 X 416 55 65 75 281 BC
4-4-6 7 12 790 X 481 70 85 95 100 420 BC
3-3-5 7 15 843 X 508 85 100 110 110 515 BC
2-2-4 7 12 929 X 563 95 115 130 125 639 BC
Table values reflect XHHW-2 conductors Package Code: A-250’B-500′ C-1,000′ D-100’E- 150′
Allowable ampacities shown are for general use as specified by the National Electrical Code, 2011 Edition, section 310.15 and 240.4(D).
Unless the is marked for use at higher temperatures the conductor ampacities shall be limited to the following per NEC 110.14(C)
60 °C When terminated to equipment for circuits rated 100 amperes or less or marked for 14 – 1 AWG conductors.
75 °C When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.
90 °C XHHW wet or Dry locations for ampacity adjustment purposes using NEC section 310.15 For dwelling ampacity use section 310.15(B)(7)

Why Choose Us

Please feel free to leave your requirement, We will reply you in 12 hours.

    Your Name

    Your Email *

    Your Phone Number

    Your Country

    Your Requirement *

    whatapp-icon
    email-icon
    Inquiry

      sales@huadongcablegroup.com

      Name

      Email *

      Phone

      Requirement *

      X