Temperature: 105°C
Conductor: Annealed bare copper Compressed, Class B stranding
Extruded Strand Shield: Extruded thermoset semi-conducting stress-control layer over conductor
Insulation: Ethylene Propylene Rubber (EPR)
Extruded Insulation Shield: Thermoset semi-conducting polymeric layer free stripping from insulation
Grounding Conductor: 1-3 bare or covered grounding conductors may be supplied in the twisted assembly upon request
Metallic Shield: 5 mils annealed copper tape with an overlap of 25%
Jacket: Flame-retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC)
Applications:
• Suitable for use in a broad range of commercial, industrial, and utility applications, where reliability is the major concern, space is limited, and ease of installation is critical
• Suitable for use in wet or dry locations when installed in accordance with the NEC For use in aerial, direct burial, conduit, open tray, and underground duct installations
MV-105-133% (5kV) or 100% (8kV) EPR Insulation PVC Jacket – Single Conductor
Temperature: 105°C
Conductor: Annealed bare copper Compact, Class B stranding
Extruded Strand Shield: Extruded thermoset semi-conducting stress control layer over conductor
Insulation: Ethylene Propylene Rubber (EPR)
Extruded Insulation Shield: Thermoset semi-conducting polymeric layer free stripping from insulation
Metallic Shield: 5 mils annealed copper tape with an overlap of 25%
Jacket: Flame-retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC)
Applications:
1 Suitable for use in wet or dry locations in accordance with NEC
2 For use in aerial, direct burial, conduit, open tray, and underground duct installations
3 For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4(A)(5)
MV 105 15kv cable, Jacketed-Red Identification Stripes, 100% and 133% Insulation Levels
Temperature: 105°C
Conductor: Compressed or Compact Round Copper
Strand Screen: Extruded Semiconducting EPR
Insulation: EPR
Insulation Screen: Extruded Semiconducting EPR
Concentric Conductor: Bare Copper Wires
Jacket: Black with red extruded stripes
Applications:
cables provide maximum circuit longevity in underground residential distribution systems. They can be buried direct or installed in underground ducts or conduits.
Data Sheet of MV-105 – 133% Insulation Level, 3-Conductor
Gauge | Conductors | Stranding | Ground Gauge | Insulation Thickness | Jacket Thickness | Outside Diameter Inches | Material Weight (Lbs./M’) |
6 | 3 | 7 | 6 | 0.115 | 0.08 | 1.29 | 939 |
4 | 3 | 7 | 6 | 0.115 | 0.08 | 1.39 | 1163.7 |
2 | 3 | 7 | 6 | 0.115 | 0.08 | 1.51 | 1471.5 |
1/0 | 3 | 19 | 4 | 0.115 | 0.11 | 1.67 | 1978.1 |
2/0 | 3 | 19 | 4 | 0.115 | 0.11 | 1.82 | 2282.8 |
4/0 | 3 | 19 | 3 | 0.115 | 0.11 | 2.07 | 3298.6 |
250 | 3 | 37 | 3 | 0.115 | 0.11 | 2.15 | 3773.7 |
350 | 3 | 37 | 2 | 0.115 | 0.11 | 2.36 | 4844 |
500 | 3 | 37 | 1 | 0.115 | 0.11 | 2.64 | 6370.7 |
750 | 3 | 61 | 1/0 | 0.115 | 0.14 | 3.14 | 9279.3 |
Data Sheet of MV-105 EPR Insulation, PVC Jacket – Single Conductor
Gauge | Stranding | Insulation Diameter Min | Insulation Diameter Max | Insulation Thickness | Jacket Thickness | Outside Diameter Inches | Material Weight (Lbs./M’) |
6 | 7 | .415″ | .490″ | 0.115 | 0.06 | 0.65 | 294.5 |
4 | 7 | .455″ | .535″ | 0.115 | 0.06 | 0.7 | 365.4 |
2 | 7 | .510″ | .590″ | 0.115 | 0.06 | 0.76 | 467.9 |
1/0 | 19 | .580″ | .655″ | 0.115 | 0.06 | 0.82 | 620.1 |
2/0 | 19 | .620″ | .695″ | 0.115 | 0.06 | 0.86 | 721.5 |
3/0 | 19 | .665″ | .745″ | 0.115 | 0.08 | 0.94 | 877.8 |
4/0 | 19 | .720″ | .795″ | 0.115 | 0.08 | 1 | 1038.2 |
250 | 37 | .770″ | .850″ | 0.115 | 0.08 | 1.05 | 1182.3 |
350 | 37 | .970″ | .945″ | 0.115 | 0.08 | 1.14 | 1537.1 |
500 | 37 | .990″ | 1.065″ | 0.115 | 0.08 | 1.27 | 2024.7 |
750 | 61 | 1.170″ | 1.250″ | 0.115 | 0.08 | 1.45 | 2917.8 |
1000 | 61 | 1.320″ | 1.400″ | 0.115 | 0.08 | 1.6 | 3765.1 |
Why Choose Us